6. From the Main configuration Menu,
A - Select the NETWORK PROTOCOL: Enusre DH+ is
selected.
The settings here depend on Which model of the
DL3500 you are configuring, the DSS-Bridge or
the CRANE-Bridge.
1- DSS Bridge
– Units connected to
the DSS DH+ network and have unique DH+
node numbers on the highway.
Configure the Following:
• The appropriate DH+ network speed.
• The station number that the DL3500 will be
occupying on the network (ensure that this
station is available and that there are no
conflicts with other devices or PLC’s).
• Under “DF1 Serial/USB Communication
Protocol” the channel serial speed is hard
coded to always be 115.2 KBaud.
• Leave all settings Under SET/CHANGE SERIAL
PARAMETERS and SET DF1 ADVANCED
PARAMETERS to there defaults.
When all options have been selected press the
DOWNLOAD TO DL BUTTON
2- CRANE Bridge
– Units
connected to the individual CRANE DH+
networks have hard coded DH+ node
numbers on the highway.
Configure the Following:
• The appropriate DH+ network speed.
• The station number that the DL3500 will be
occupying on the network is always going to
be 01. The CRANE PLC must always be 22
(octal) to ensure correct communications.
• Under “DF1 Serial/USB Communication
Protocol” the channel serial speed is hard
coded to always be 115.2 KBaud.
• Leave all settings Under SET/CHANGE SERIAL
PARAMETERS and SET DF1 ADVANCED
PARAMETERS to there defaults.
When all options have been selected press the
DOWNLOAD TO DL BUTTON
The following applies to both Models:
7. In the
Status Bar there should be an A-OK
Parameters transferred successfully. Once
this is seen, Select
Return to Main Menu
and then
Exit DL32 to exit the program.
8. If you wish to save the
Configuration
Settings then select the
CONFIGURATION
Settings button and choose
Save
Configuration Settings.
9. The DL3500 is ready for normal operation on
your network. Hit the
RESET button to bring
the DL3500 On-Line.